Home      Products     Endress+Hauser     Level       FTL51C Vibronic Point level detection
  • FTL51C Vibronic Point level detection

FTL51C Vibronic Point level detection

  • Product Item : FTL51C-AYY9DL4E6AA
  • Category: Level
  • Measuring Principle:Vibration Liquids
  • Characteristic / Application :Liquiphant M Density with Density Computer FML621 Temperature and Pressuremeasurement Modular housing concept wide range of process connections pipe extension up to 3m (6
  • Sensor length:115...3000mm >3000...6000mm (Option) 
  • Output:Pulse 
  • INQUIRY   EMAIL
C=coating,comparing to FTL51,FTL51C has highly corrosion-resistant coating, so it can be used in corrosive liquids field.

Vibronic Point level detection Liquiphant FTL51C

Point level switch for liquids with highly corrosion-resistant coating


Liquiphant FTL51C is a point level switch with extension tube and highly corrosion resistant coating. For use in hazardous areas with all international certificates. Useable in all industries. FTL51 offers functional safety SIL2/SIL3. With the second line of defense highest degree of safety and availability of the device can be guaranteed. Reliable measurement values, not affected by: changing media properties, flow, turbulences, gas bubbles, foam, vibrations or build-up.

 

Benefits

  • Use in safety systems requiring functional safety to SIL2/SIL3 in accordance with
    IEC 61508/IEC 61511-1

  • Different plastic coating (PFA) and enamel coating for applications with aggressive medias

  • International explosion protection certificates and overfill prevention certificate (WHG)

  • No calibration required, easy to start up

  • No mechanically moving parts: no maintenance, no wear, long operating life.
    Monitoring of fork for damage: guaranteed function

  • Second line of defense to protect the environmental

  • Variety of standardized process connections for all applications

Field of application

Point level switch for all liquids with highly corrosion-resistant coating.

  • Process connections: Flanges and hygienic process connection (FDA conform with PFA)

  • Temperature: -50 to +150°C (-58 to +302°F)

  • Pressure: -1 to +40bar (-14.5 to +580psi)

  • Sensor material: ECTFE, PFA (Edlon, Rubyred, conductive), Enamel

  • International explosion protection certificates, overfill prevention WHG, SIL, hygienic certificates, marine approvals

Features and specifications

Density measurement
Measuring Principle Vibration Liquids
Characteristic / Application Liquiphant M Density with Density Computer FML621 Temperature and Pressure measurement
High protection against aggressive media by using antistatic coating Modular housing concept wide range of process connections
pipe extension up to 3m (6m option)
for compensation (option)
Supply / Communication Transmitter power supply (MUS)
Ambient temperature -50...80°C
-50...60°C for hazardous applications
Process temperature 0...80 °C (validity of accuracy data)
-50...0°C / 80...150 °C (with reduced technical data)
Process pressure absolute 0...25bar
>25...40bar (with reduced technical data)
Wetted parts ECTFE, PFA and Enamel
Sensor length 115...3000mm
(depends by the covering)
Output Pulse
Certificates / Approvals ATEX
IECEx
Options Commissioning with ReadWin2000
Components Density Computer FML621
Point Level measurement/Liquids Level meter
Measuring Principle Vibration Liquids
Characteristic / Application High protection against aggressive media by using antistatic coating
Modular housing concept
wide range of process connections
Analogue and bus interfaces
Extensive certificate range (e.g.Ex,WHG)
pipe extension up to 3m (6m option)

Supply / Communication PROFIBUS PA
19...253V AC, 2-wire
10...55V DC-PNP, 3-wire
DPDT, 19...253V AC, 10...55V DC
8/16mA, 11...36V DC
NAMUR
PFM, 2-wire
NAMUR with testbutton
Ambient temperature -50 °C...+70 °C
(-58 °C...+158 °F)
Process temperature -50 °C...+150 °C
(-58 °F...+302 °F)
up to 230 °C / 450°F on request
Process pressure absolute / max. overpressure limit Vacuum...40 bar
(Vacuum...580 psi)
Min. density of medium 0.5g/cm³ (0.4g/cm³ optional)
Main wetted parts ECTFE
PFA (Edlon)
PFA (Rubyred)
PFA (conductive)
Enamel
Process connection Flange:
DN25...DN100,
ASME 1"...3",
JIS RF10 K 50
Process connection hygienic FDA conform with PFA (Edlon)
Sensor length ECTFE, PFA 130mm, 148mm...3000mm
(ECTFE, PFA 5.12", 5.83"...118")
Enamel 130mm, 148mm...1200mm
(Enmal 5.12", 5.83"...47.24")
Output PROFIBUS PA
19...253V AC
10...55V DC-PNP
19...253V AC bzw 10...55V DC
8/16mA, 11...36V DC
NAMUR
PFM
Certificates / Approvals ATEX, FM, CSA, NESPI, TIIS, INMETRO
Overfill prevention WHG
SIL
EN10204-3.1
GL/ABS marine
FDA listed
Options Heavy duty stainless steel housing mainly for the oil and gas industry

Specialities Foamdetection
Detekt a densitychange
second line of defense

Components FTL325P/FTL375P Interface PFM
FTL325N/FTL375N Interface NAMUR