Field of application
The Prosonic FMU44 sensor is suited for non-contact level measurement in fluids, pastes, coarse bulk material and flow measurement in open channels or at weirs. The two-wire or four-wire compact transmitter can be used in applications with storage tanks, agitators, on stockpiles and conveyor belts. The envelope curve can be shown on the on-site display for simple diagnosis. Linearization function (up to 32 points) for conversion of the measured value into any unit of length, volume or flow rate.
Two-wire or four wire instrument for continuous non-contact level and flow measurement.
-
Process connection: Flange
-
Temperature: -40 to +80°C (-40 to +176°F)
-
Pressure: +0.7 to +2.5bar (+10 to +36psi)
-
Maximum measuring distance: Liquids 20m (66ft), Solids 10m (33ft)
-
Blocking distance: Liquids and Solids 0.5m (1.9ft)
-
International explosion protection certificates
Benefits
-
Reliable non-contact measurement
-
Quick and simple commissioning via menu-guided on-site operation with four-line plain text display, 7 languages selectable
-
Envelope curves on the on-site display for simple diagnosis
-
Hermetically sealed and potted sensor
-
Chemically resistant sensor out of PVDF
-
Calibration without filling or discharging
-
Integrated temperature sensor for automatic correction of the temperature dependent sound velocity
|
Benefits
-
Reliable non-contact measurement
-
Quick and simple commissioning via menu-guided on-site operation with four-line plain text display, 7 languages selectable
-
Envelope curves on the on-site display for simple diagnosis
-
Hermetically sealed and potted sensor
-
Chemically resistant sensor out of PVDF
-
Calibration without filling or discharging
-
Integrated temperature sensor for automatic correction of the temperature dependent sound velocity
|
-
-
Characteristic / Application
Compact ultrasonic transmitter
-
-
Accuracy
+/- 4mm or +/- 0,2 % of set measuring range
-
Ambient temperature
-40 °C ... 80 °C
(-40 °F ... 176 °F)
-
Process temperature
-40 °C ... 80 °C
(-40 °F ... 176 °F)
-
Process pressure / max. overpressure limit
0,7 bar ... 2,5 bar abs
(10 psi ... 36 psi)
-
-
Process connection
Flange
DN100, ASME 4", JIS 10K 100
DN150, ASME 6", JIS 10K 150
DN200, ASME 8", JIS 10K 200
Mounting bracket
-
-
Max. measurement distance
Liquids: 20 m (66 ft),
Solids: 10 m (33 ft)
-
-
Certificates / Approvals
ATEX, FM, CSA, INMETRO, NEPSI
-
Application limits
Fast filling and discharging rate:
FMU90 + FDU9x
Level limit detection:
FMU90 + FDU9x
|
FMU44-ATB2A22A
-
Approval
A
Non-hazardous area
-
Process Connection
T
UNI flange 4"/DN100/100, PPmax 2.5bar abs./ 36psia, suitable forNPS 4" Cl.150 / DN100 PN16 / 10K 100
-
Power Supply; Output
B
2-wire; 4-20mA HART
-
Operation
2
4-line display VU331,envelope curve display on site
-
Housing
A
F12 Alu, coated, IP68 NEMA6P
-
Cable Entry
2
Gland M20 (EEx d > thread M20)
-
Process Sealing Sensor / Flange
2
FKM Viton
-
Additional Option
A
Basic version
|
|
|
|
|