Home      Products     Allen-Bradley       Allen Bradley 1756-OX8I Output Module Co

Allen Bradley 1756-OX8I Output Module ControlLogix

  • Product Item : 1756-OX8I
  • Category: Allen-Bradley
  • Voltage type of supply voltage:DC
  • Type of digital output:Relay
  • Outputs:8 N.O., 8 N.C. individually isolated (two points per group)
  • States in fault mode per point:Hold last state, On or Off (Off is default)
  • INQUIRY   EMAIL

Catalog #: 1756-OX8I

Output Module, ControlLogix, Relay Digital, 8 Point, 8 Normally Open/Normally Closed, Individually Isolated Contacts



Technical Specifications

Electrical

Suitable for safety functions No
Digital inputs configurable No
Digital outputs configurable No
Voltage type of supply voltage DC
Type of voltage (input voltage) DC
Type of digital output Relay
Type of electric connection Screw connection
Bounce time, mean 1.2 μs
Total backplane power 2.9 W
Thermal dissipation 10.57 BTU/h
Current draw 100 mA @ 5.1V, 100 mA @ 24V
Expected contact life 300 kHz, resistive, 100 kHz, inductive
Module keying Electronic, software configurable
Outputs 8 N.O., 8 N.C. individually isolated (two points per group)
Scheduled outputs Synchronization within 16.7 s max, reference to the coordinated system time
Power dissipation, max 3.1 W @ 60 °C (140 °F)
Contact current rating 1 A @ 5...30V DC, 0.5 A @ 48V DC, 0.22 A @ 125V DC, 1.5 A @ 120V AC, 50/60 Hz, 0.75 A @ 240V AC, 50/60 Hz
Isolation voltage 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
Wire category Wire category: 1
Fusing Not protected. A fused IFM is recommended to help protect outputs
Redundancy No
Short-circuit protection, outputs available No
Pilot duty C300, R150
Initial contact resistance, max 100 mΩ @ 6V, 1 A
Switching frequency, max 1 operation/3 s (0.3 Hz at rated load)
States in fault mode per point Hold last state, On or Off (Off is default)
States in program mode per point Hold last state, On or Off (Off is default)

Mechanical

Slot width 1
RTB keying User-defined mechanical
Shock Operating: 30 G, Non operating: 50 G
Vibration 2 G @ 10...500 Hz

Environmental

Surrounding air temperature, max 60 °C
North American temperature code T4A
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges, 8 kV air discharges
Relative humidity 5...95% noncondensing
Conducted RF immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity ±4 kV at 5 kHz on signal ports
Operating temperature 0 to 60 °C
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Radiated RF immunity 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Nonoperating temperature -40 °C
Oscillatory surge withstand IEEE C37.90.1: 3kV

Output Specifications

Off-state leakage current per point, max 0 mA
Load current per point, min 10 mA
Output delay time OFF to ON: 13 ms maximum, ON to OFF: 13 ms maximum

Input Specifications

Operating voltage 5...125V DC, 10...240V AC

Construction

Enclosure type None (open-style)

Certifications

  • Safety
  • CE